
4
2. Installation and storage
■
Installation and storage
1.
Storage: If the equipment is not to be installed immediately, it should be stored in a clean and dry
location at ambient temperatures from 20℃to 55℃. The surrounding air must be free of corrosive
contaminants. And please input power a time per half year.
2. Installation place: Places where the peripheral temperature is from -10℃to 40℃, and where the
relative humidity is 90% or less. Avoid installing at places where there is dust, iron particles,
corrosive gas, water spray, direct sunlight or too much vibration. And places where has good
ventilation.
3. Please fix the inverter under the cooling fan if it is installed in the panel. The heating from inverter
will be discharged out of the panel to reduce the temperature and get the better effect of ventilation.
Notice : 10HP(contained) and above inverter are installed as following.
30 cm at least
10cm
10cm
10~20 cm
CT2000F
□
FAN
Discharge heating
Heating of inverter