52
◆Jog frequency
Description: To control jog, must comply external operation Cd04=1, and use external terminal FR or RR
and COM shorted, or use FORWARD JOG (FJOG), REVERSE JOG (RJOG).
1. Jog operation is valid only when operation command selects the external operation single mode
(eg. Cd04=1) and set Cd92 Cd97=5, jog operation procedures:
1. First put external terminal in, then FR (or RR)
2. Put external terminal and FR ( or RR) simultaneously, be sure always to put in external terminal
before FR (or RR)
External terminal
FR/RR
Running mode Jogging
2. When set Cd92 Cd97= 6、7 (FJOG/ RJOG), jog without putting FR (or RR) in.
External terminal
FJOG/ RJOG
Running mode Jogging
Jog acceleration/ deceleration time : set the climbing time of frequency from 0HZ to 50HZ
(T) =
(50 - 0)
F
△
×
T1
T1:Time needed for accelerate / decelerate
△F:Frequency changed
9. Output/ input terminals ■
Constant
No.
Constant name
Settable range
Factory setting
Change during
operation
Cd15 Jog
frequency 0.0 240.0
5.0 O
Cd19
Jog acceleration/ deceleration time
0.0 6000.0
1sec
O
Setting value