◆Multi-functions relay setting
Description: Set multi-functions output contactor function.
Cd29 (TIME): This function must accommodate Cd47, 48=0 setting. When motor starts operation, the time
counter is active.
Cd45 (Frequency detect level) : accommodate Cd47, 48=6, Cd45 will appoint the action level.
1
CD45
FA-FC
OPEN
CLOSE
Time
HZ OUTPUT
Time
Cd47, 48 could be set the function by Multi-functions ouput contactor, please refer to the list:
Setting Function
0
Time counter (accommodate Cd29)
1 Fault
2 Stop
3 Acceleration
4 Speed
reached
5 Deceleration
6
Frequency reached (operation frequency>Cd45)
7
Current reached (compare to Cd85 and Cd86 value)
8
Over heating prediction action(Cd82×Cd84)
9
OL fault action
10 No
action
9. Output/ input terminals ■
Constant
No.
Constant name
Settable range
Factory setting
Change during
operation
Cd29 TIME 0 60000 5
X
Cd45 Frequency
detect
level 0.00 400.00
0.50
X
Cd47
Multi-functions relay 1
0 10
1
X
Cd48
Multi-functions relay 2
0 10
1
X
Cd49
Multi-functions relay DO
0 10
8
X