11
Wiring diagram
◆ Wiring the master circuit and control circuit
Wire according to the standard connection diagram. On using the external sequence control, please
use small signal relay or double terminal relay to avoid relay terminal malfunction.
◆ Signal wire
The signal circuit uses either shielded pairs or twisted pairs, should be wired either using a wiring
duct separated from that for the power circuit, or with the wiring conduit isolated as much as
possible.
◆ Wiring between main circuit and motor
Connect the main circuit, by wiring according to the main circuit terminal connection diagram. Care
is required not to make a mistake when connecting the input and output terminals, lest it will cause
inverter damage. Specifications of main circuit path and NFB are as following:
*CT2000F□
Voltage
(V)
Model NFB
(A)
Standard wiring
(mm
2
)
CT-2000FG-2-3A7 20
5.5
CT-2000FG-2-5A5 30
5.5 8
CT-2000FG-2-7A5 40
5.5 8
CT-2000F□-2-011 60
22
CT-2000F□-2-015 80
30
CT-2000F□-2-022 120
38
CT-2000F□-2-030 150
38 100
CT-2000F□-2-037 200
38 100
CT-2000F□-2-045 250
60 100
CT-2000F□-2-055 300
100
CT-2000F□-2-075 400
100 200
CT-2000F□-2-093 500
100 200
CT-2000F□-2-112 500
100 200
CT-2000FG-2-131 600
100 200
220
CT-2000FG-2-150 600
200
Voltage
(V)
Model NFB
(A)
Standard wiring
(mm
2
)
CT-2000FG-4-3A7
10 3.5 5.5
CT-2000FG-4-5A5
15 3.5 5.5
CT-2000FG-4-7A5
20 5.5
CT-2000F□-4 -011
30
8 14
CT-2000F□-4-015
40 8 14
CT-2000F□-4-022
60 22
CT-2000F□-4-030
80 22
CT-2000F□-4-037
100 30
CT-2000F□-4-045
120 50
CT-2000F□-4-055
150 38 100
CT-2000F□-4-075
200 38 100
CT-2000F□-4-093
250 60 100
CT-2000F□-4-112
300 60 100
CT-2000F□-4-131
300 100
CT-2000FG-4-150
400 100 200
CT-2000FG-4-188
400 100 200
380
|
460
CT-2000FG-4-225
500 100 200
No. Specification
G 150%
load
P 120%