8.6 Humidity
Options
The “Humidity Options” screen is accessed from the “Chamber” menu. This screen is used to define
what type of humidity system the chamber has and how the EZT-570i is to control it.
Figure 8-11 Humidity Options
You must press the “Set” button to save changes to the humidity system type selection. Be
sure to press the “Set” button prior to switching to another configuration screen or any
change to the humidity system type will not be saved.
Parameter Descriptions
Humid Type:
Sets the type of humidity system installed on the chamber.
- “Humidity Installed” is for single stage/tundra systems or cascade systems
without a separate RH cooling circuit on system 1.
- “Single stage humid installed” is for cascade systems that run in single
stage mode during humidity (have separate RH cooling circuit on system 1).
Cmp On %:
Sets the loop percentage of output required to enable the refrigeration system in
order to provide dehumidification.
Cmp On Dly:
Sets the delay in seconds for which the loop percentage of output must exceed
the cmp on % before the refrigeration system is turned on.
Cmp Off %:
Sets the loop percentage of output required to disable the refrigeration system
because dehumidification is no longer required.
Cmp Off Dly:
Sets the delay in seconds for which the loop percentage of output must exceed
the cmp off % before the refrigeration system is turned off
Hum Min SP:
Sets the minimum air temperature set point at which the humidity system will
operate. When the air temperature set point and/or air temperature is below this
value, the humidity system will be automatically turned off and the system status
indicator “RH TMP DISABLE” will be lit.
Содержание EZT-570i
Страница 1: ...EZT570i Technical Manual Rev B EZT 570i Technical Manual...
Страница 14: ...EZT 570i Technical Manual 14 4 1 6 Conditioning System Logic Flow...
Страница 15: ...EZT 570i Technical Manual 15...
Страница 19: ...EZT 570i Technical Manual 19 4 2 2 Humidity System Logic Flow...
Страница 21: ...EZT 570i Technical Manual 21 4 3 2 Auxiliary Cooling System Logic Flow...
Страница 23: ...EZT 570i Technical Manual 23 4 4 2 Dry Air Purge System Logic Flow...
Страница 25: ...EZT 570i Technical Manual 25 4 5 2 Altitude System Logic Flow...
Страница 29: ...EZT 570i Technical Manual 29 4 7 2 Transfer System Logic Flow...
Страница 30: ...EZT 570i Technical Manual 30...
Страница 58: ...EZT 570i Technical Manual 58 7 2 Standard Output Configuration...
Страница 92: ......
Страница 93: ...EZT 570i Technical Manual 1 Appendix...