EZT-570i Technical Manual
59
7.2.1 Output Description of Use
Audible Alarm (Q0):
This output is used to turn the audible alarm on and off under
fault conditions.
Maximum Cool Enable (Q1):
This output is used to enable and disable the maximum cooling
solenoids based on the percentage of output set up in the
configurator. When the loop output exceeds the maximum
output on percentage for the on delay period set in the
configurator, this output will turn on.
Air Circulator(s) (Q2):
This output is used to turn the chamber air circulator(s) on and
off when the chamber event 1 is turned on and off. If defrost is
enabled, this output will turn off the air circulator(s) during defrost
and will turn back on once defrost is complete.
System 1 Compressor (Q3):
This output is used to turn system 1 compressor on and off
based on the demand for cooling or dehumidification. The
output turns on when the loop percentage of output exceeds the
on percentage for the delay period set in the configurator. The
output will turn off the compressor when the loop percentage of
output exceeds the off percentage for the delay period set in the
configurator.
The output also turns on and off with the pressure switch input
(I32) if pumpdown is enabled. If main power is off for more than
30 minutes, the input will be ignored, and the output will remain
off, until pumpdown is reset automatically after 4 hours or
manually by the operator.
The output is also controlled by the defrost pressure switch (I40).
When defrost is enabled, the output will turn system 1
compressor on and off with the input in order to maintain the
discharge pressure of system 2 at the proper range during
defrost. Note that when large horsepower defrost is enabled, the
output will remain on at all times and is not cycled on and off.
System 2 Compressor (Q4):
This output is used to turn system 2 compressor on and off
based on the demand for cooling. It turns on after the stager
start delay time set in the configurator. The timer begins once
system 1 output turns on. The output turns off when system 1
output turns off.
During single stage humidity operation, the output is also turned
off. The output will remain off until humidity is turned off. The
stager start timer will begin again and turn on the output.
During defrost, the output is forced on to maintain system 2
operation in order to provide hot gas for defrosting of the cooling
coils. Once defrost is complete, the output will be controlled by
normal cooling requirements.
Содержание EZT-570i
Страница 1: ...EZT570i Technical Manual Rev B EZT 570i Technical Manual...
Страница 14: ...EZT 570i Technical Manual 14 4 1 6 Conditioning System Logic Flow...
Страница 15: ...EZT 570i Technical Manual 15...
Страница 19: ...EZT 570i Technical Manual 19 4 2 2 Humidity System Logic Flow...
Страница 21: ...EZT 570i Technical Manual 21 4 3 2 Auxiliary Cooling System Logic Flow...
Страница 23: ...EZT 570i Technical Manual 23 4 4 2 Dry Air Purge System Logic Flow...
Страница 25: ...EZT 570i Technical Manual 25 4 5 2 Altitude System Logic Flow...
Страница 29: ...EZT 570i Technical Manual 29 4 7 2 Transfer System Logic Flow...
Страница 30: ...EZT 570i Technical Manual 30...
Страница 58: ...EZT 570i Technical Manual 58 7 2 Standard Output Configuration...
Страница 92: ......
Страница 93: ...EZT 570i Technical Manual 1 Appendix...