EZT-570i Technical Manual
52
monitor screen) and the input is off (requires manual reset of E-
Stop button).
Fluid Temperature Safety (I44):
The fluid system temperature safety input is used to indicate that
the fluid temperature limit has been exceeded (LC chambers).
This input is active high, i.e., the input must be on in order for the
alarm to be indicated. When active (input on), the EZT shuts
down the chamber until the alarm is acknowledged (silence
button pressed on alarm monitor screen) and the input is off
(requires manual reset of limit device).
Fluid Pressure Safety (I45):
The fluid system pressure safety input is used to indicate that the
fluid system has exceeded maximum operating pressures (LC
chambers). This input is active low, i.e., the input must be off in
order for the alarm to be indicated. When active (input off), the
EZT shuts down the chamber until the alarm is acknowledged
(silence button pressed on alarm monitor screen) and the input is
off.
Fluid Flow Safety (I46):
The fluid system flow safety input is used to indicate that the fluid
system has proper flow (LC chambers). This input is active low,
i.e., the input must be off in order for the alarm to be indicated.
When active (input off), the EZT shuts down the chamber until
the alarm is acknowledged (silence button pressed on alarm
monitor screen) and the input is off.
The EZT has a built in time delay to disable the low flow alarm
until the pump has had a chance to start and begin moving fluid
(5 seconds). If the input does not turn on within the start delay
period, the alarm will be activated.
Power Failure(I47):
The power failure input is used to indicate that there is a primary
power failure to the chamber. When the chamber is equipped
with a battery backup option for the control circuit, it allows the
EZT to send out an alarm message over its network interface to
alert operators of the power outage. When main power is
restored, the EZT will automatically restart the chamber.
Содержание EZT-570i
Страница 1: ...EZT570i Technical Manual Rev B EZT 570i Technical Manual...
Страница 14: ...EZT 570i Technical Manual 14 4 1 6 Conditioning System Logic Flow...
Страница 15: ...EZT 570i Technical Manual 15...
Страница 19: ...EZT 570i Technical Manual 19 4 2 2 Humidity System Logic Flow...
Страница 21: ...EZT 570i Technical Manual 21 4 3 2 Auxiliary Cooling System Logic Flow...
Страница 23: ...EZT 570i Technical Manual 23 4 4 2 Dry Air Purge System Logic Flow...
Страница 25: ...EZT 570i Technical Manual 25 4 5 2 Altitude System Logic Flow...
Страница 29: ...EZT 570i Technical Manual 29 4 7 2 Transfer System Logic Flow...
Страница 30: ...EZT 570i Technical Manual 30...
Страница 58: ...EZT 570i Technical Manual 58 7 2 Standard Output Configuration...
Страница 92: ......
Страница 93: ...EZT 570i Technical Manual 1 Appendix...