EZT-570i Technical Manual
73
Heat Dly:
Sets the delay in seconds for which the loop percentage of output must exceed
the max heat% before the max heat output will turn on.
Max Cool%:
Sets the loop percentage of output at which the maximum cool output is enabled.
Cool Dly:
Sets the delay in seconds for which the loop percentage of output must exceed
the max cool% before the max heat output will turn on.
The EZT automatically assigns the digital outputs of additional relays cards for specific
options as enabled in the configurator. For a standard dry chamber (non-humidity) that does
not have a maximum heat circuit, the “max heat%” and “heat dly” should be set at zero.
This insures that when the first relay card is added, the outputs will be used for the customer
event option. If the max heat settings are not zero, or another option is installed that uses the
outputs on the first 16-output relay card, the second 16-output relay card will be used for
customer events if installed.
Содержание EZT-570i
Страница 1: ...EZT570i Technical Manual Rev B EZT 570i Technical Manual...
Страница 14: ...EZT 570i Technical Manual 14 4 1 6 Conditioning System Logic Flow...
Страница 15: ...EZT 570i Technical Manual 15...
Страница 19: ...EZT 570i Technical Manual 19 4 2 2 Humidity System Logic Flow...
Страница 21: ...EZT 570i Technical Manual 21 4 3 2 Auxiliary Cooling System Logic Flow...
Страница 23: ...EZT 570i Technical Manual 23 4 4 2 Dry Air Purge System Logic Flow...
Страница 25: ...EZT 570i Technical Manual 25 4 5 2 Altitude System Logic Flow...
Страница 29: ...EZT 570i Technical Manual 29 4 7 2 Transfer System Logic Flow...
Страница 30: ...EZT 570i Technical Manual 30...
Страница 58: ...EZT 570i Technical Manual 58 7 2 Standard Output Configuration...
Страница 92: ......
Страница 93: ...EZT 570i Technical Manual 1 Appendix...