EZT-570i Technical Manual
66
System 2B Compressor (Q47):
This output is used to turn system 2B compressor on and off
based on the demand for cooling. It turns on after the stager
start delay time set in the configurator. The timer begins once
system 1B output turns on. The output turns off when system 1B
output turns off.
During single stage humidity operation, the output is also turned
off. The output will remain off until humidity is turned off. The
stager start timer will begin again and turn on the output.
During defrost, the output is forced on to maintain system 2B
operation in order to provide hot gas for defrosting of the cooling
coils. Once defrost is complete, the output will be controlled by
normal cooling requirements.