68
Fault elimination
Code
Message
Information
Warning
Error
Possible causes
Remedy
W82
E82
Driver Missing
Communication with driver board interrupted.
RS485 Bus to driver board interrupted. Contact your Condair representative.
–––
E84
Driver Defective
Unknown fault on driver board
Driver board defective.
Contact your Condair representative.
–––
E85
Driver ID Wrong
Driver board ID wrong.
Wrong driver board connected or SAB
address wrong.
Contact your Condair representative.
–––
E86
Driver
Incompatible
Wrong version of driver board.
Wrong version of driver board.
Contact your Condair representative.
–––
E87
Local 24VSupply
Local 24V voltage on driver board out of valid range!
Short circuit on supply module or supply
module defective.
Contact your Condair representative.
–––
E88
Local 5V Supply
Local 5V voltage on driver board out of valid range!
Short circuit on supply module or supply
module defective.
Contact your Condair representative.
–––
E89
Local Reference
Supply
Local reference voltage out of valid range!
DC supply faulty or supply line inter-
rupted.
Contact your Condair representative.
–––
E91
Pressure Instable
Water inlet pressure unstable!
Shut-off valve in the water supply line
not fully open.
Check/completely open shut-off
valve.
Pressure of the reverse osmosis
system too low.
Let have the reverse osmosis system
be checked/maintained/repaired.
Cross section of the supply line too
small.
Install water supply line with lager cross
section (min. ø10/12 mm).
Sterile filter clogged.
Clean sterile filter housing and replace
).
–––
E93
FC Error
Monitoring of the frequency converter has triggered.
Frequency converter overloaded, too
hot, or over current monitoring has
triggered. Error code can be checked
on frequency converter.
Contact your Condair representative.
Fuse "F1" on the driver board defec-
tive.
Pressure relief valve on booster
pump set too high.
–––
E94
FC Current
Current of the frequency converter is too high!
Booster pump or pump motor
blocked.
Contact your Condair representative.
Frequency converter or control wrong
configured.
Spray circuit valves clogged or defec-
tive.
Nozzles or spray circuit lines
clogged.
Check/clean/replace Nozzles or spray
circuit lines.
Pressure relief valve on booster
pump set too high.
Contact your Condair representative.
–––
E96
Peripheral
5V Supply
Peripheral 5V supply out of valid range.
5V supply interrupted.
Contact your Condair representative.
Fuse "F2" on the driver board defec-
tive.
Overload on external connection.
Overload due to defective pressure
sensor.