56
Maintenance and Replacement of components
6.5
Replacement of the silver cartridge "Hygiene Plus"
If the silver cartridge is exhausted and needs to be replaced Error "55 - Ag-Ion Service" is shown. Via
the "Service" relay and the "Error" relay on the remote operation and fault indication board, additionally
a maintenance request and an error is issued.
If the silver cartridge is not replaced and the counter is
not reset within 7 days
the humidification is
stopped
.
Replacing the silver cartridge
C
G
A
B
D
F
E
E
D
H
Fig. 13: Replacing the silver cartridge
1. Set the humidification system Condair DL
out of operation
as described in
and
release
the pressure in the water system
.
2. Unlock the front cover "A" of the central unit and remove the front cover.
3. Remove the two electrical connectors "B" from the connections "C" on the silver cartridge.
Содержание DL II
Страница 79: ......