Operating the Condair DL control software
5.3.3.5 Activate/deactivate the ceramic wash over function in the "Ceramic Wash Over"
submenu
CAUTION!
During the ceramic wash over the nozzles spray water onto the ceramic plates, similar to when 100%
demand is present. In systems with a booster pump, this also switches on.
This process must be monitored by the operator since the humidity can significantly exceed the desired
setpoint. Over-saturation of the ceramic plates is likely.
After the ceramic wash over is complete, any water behind the ceramic plates must be removed if it
cannot drain from there.
09/01/2021
DL
07:00 pm
Ceramic Wash Over
Spray Time
Pump Pressure
On
180 s
108.8 psi
Ceramic Wash Over
–
Ceramic Wash Over
: With this setting you activate ("On") or deactivate
("Off") the ceramic wash over function. Only when the ceramic wash over
function has been activated, ceramic wash over can be started using the
"Manual Functions" button and then the "Ceramic Wash Over" function.
Factory setting:
Off
Optional settings:
Off
or
On
–
Spray Time
: With this setting you determine the duration of the ceramic
wah over in seconds.
Factory setting:
180 s
Setting range:
1 ... 900 s
–
Pump Pressure
: With this setting you determine the pump pressure in
psi with which the booster pump provides during ceramic flushing.
Factory setting:
108.8 psi
Setting range:
58.0 ... 130.5 psi