Product specification
9
Product specification
9.1
Technical data
Condair DL
Type A
(
with
booster pump)
Type B
(
without
booster pump)
Dimensions/Weight
Installation length in AHU/duct (Min-Max)
23.62" - 35.43" (600 - 900 mm)
1)
Width AHU/duct (Min-Max)
17.72" - 330.71" (450 - 8400 mm)
2)
Height AHU/duct (Min-Max)
17.72" - 157.48" (450 - 4000 mm)
2)
Dimensions central unit HxWxD
31.50" x 20.83" x 11.22" (800 x 529 x 285 mm)
Weight central unit
approx. 119.05 lbs (54 kg)
approx. 77.16 lbs (35 kg)
Dimensions control unit HxWxD
19.09" x 13.54" x 8.54" (485 x 344 x 217 mm)
Weight control unit
approx. 33.07 lbs (15 kg)
Wet weight post-evaporation unit
approx. 11.28 lbs/ft
2
(55 kg/m
2
) humidifier area
Dry weight post-evaporation unit
approx. 8.20 lbs/ft
2
(40 kg/m
2
) humidifier area
Hydraulic
Humidification capacity
11.02 ... 2,204.62
(5 ... 1000 l/hr)
3)
11.02 ... 2,204.62 lb/hr
(5 ... 1000 l/hr)
3)
Nozzle pressure
43.5 ... 101.5 psi (3 ... 7 bar)
Nozzle sizes
8 (0.40, 0.53, 0.66, 0.79, 0.92, 1.06, 1.19 and 1.32 gal/hr at 58.0 psi /
8 (1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5 and 5.0 l/hr at 4 bar
Spray circuit valves
3/2 way NO (normally open)
Flushing water consumption
<463 lb/hr (<210 kg/hr) nozzle capacity:
0.58 - 0.66 gal/min at 58.0 psi (2.2 - 2.5 l/min at 4 bar)
<463 lb/hr (>210 kg/hr) nozzle capacity:
0.98 - 1.06 gal/min at at 58.0 psi (3.7 - 4.0 l/min at 4 bar)
Electric
Supply voltage/current control unit
200...240 VAC / 50...60 Hz,
max. 6.5 Amps
100...240 VAC / 50...60 Hz,
max. 0.5 Amps
Control booster pump motor
continuous with frequency converter
–––
Power consumption control unit
(including solonoid valves)
55 ... 65 VA
(dependent on the number of switched valves and
whether the display is in sleep mode or not)
Motor rating booster pump
approx. 12 VA per
22.05 lb/hr (10 kg/hr) spray capacity
–––
Voltage solenoid valves (Y1-Y10)
24 V DC
Frequency converter
Yes
No
Control signals
0-5 VDC, 1-5VDC, 0-10 VDC, 2-10 VDC, 0-16 VDC, 3.2-16 VDC, 0-20 VDC,
4-20 VDC, 0-20mA, 4-20 mA
Control accuracy
4)
7-steps: ±3 %rh and 15-steps: ±2 %rh 7-steps: ±4 %rh and 15-steps: ±3 %rh
Number of steps (humidity control)
Number
of steps
Possible humidifier
capacity range
lb/hr (kg/hr)
min.
cross section
inch
2
(m
2
)
max. capacity
at min. cross section
5)
lb/hr (kg/hr)
3
11.02 - 22.05
(5 - 10)
310
(0.2)
22.05
(10)
7
>22.05 - 1'234.58
(>10 - 560)
620
(0.4)
99.21
(45)
15
>55.12 - 2'204.62
(>25 - 1000)
1'705
(1.1)
218.26
(99)
31
>121.25 - 2'204.62
(>55 - 1000)
2'790
(1.8)
449.74
(204)
Содержание DL II