59
Maintenance and Replacement of components
7. Vent the sterile filter:
After replacement of the sterile filter cartridge or when the filter housing has been opened the sterile
filter must be vented. Proceed as follow:
E
D
Fig. 15: Venting the sterile filter
• Set the humidification system Condair DL into operation as described in
Important
: a minimum flow pressure of 43.51 psi (3.0 bar) must present in the water supply line.
• Perform a manual flushing cycle (see
). As soon as an acoustic noise is audible
from the water flow press the red venting knob "E" on top of the filter housing cover "D" (see
) until water (without air) is pouring out.
Note: If an error message is active the malfunction must be eliminated before a the flushing can
be performed.
• Check the filter housing for leaks.
• If necessary, stop manual flushing cycle.
8. Attach the front cover of the central unit "A" and lock it with the screw.