Operating the Condair DL control software
5.1.1 Device status indication field
If you press the device status field in the home screen, a window appears with further information on
the device status.
09/01/2021
DL
07:00 pm
Home
Next Maintenance
1685 hr
Demand
Standby
0%
09/01/2021
DL
07:00 pm
Device Status
Error Status
Max. Hum. Capacity
Actual Hum. Capacity
Standby
No Error
176.4 lb/hr
0 lb/hr
Winterzeit
Status
–
Device Status
: Shows the current device status.
–
Error Status
: Shows the current error status
("No Error", "Warning" or "Error").
–
Max. Hum. Capacity
: Shows the maximum
humidification output of the Condair DL in lb/hr.
–
Actual Hum. Capacity
: Shows the current hu-
midification output of the Condair DL in lb/hr.
The following error status symbols may be shown:
Error status symbol
Description
The Condair DL works perfectly.
A malfunction with the status "Warning" has occurred.
A malfunction with the status "Error" has occurred. Depending on the error, the operation of the
Condair DL is stopped, or it continues to work to a limited extent.
The following device status indications may appear:
Device status
Description
Initializing
The control is initalising.
Stopped
The humidification system was stopped due to a malfunction that makes it impossible to con-
tinue operation.
Flushing
The water system is being flushed.
Standby
No humidity demand for more than 60 minutes the humidification system is in standby mode. The
water system is flushed automatically for 120 seconds before the next humidification takes place
Humidifying
The humidification system is humidifying.
Ready
The humidification system is flushed and ready to humidify immediately if a demand is present.
Air Pressure Cleaning
The optional air cleaning is in progress.
Filling
The humidification system is filling and deaerating after water shortage has occured.
Conductivity Flush
The conductivity of the supply water is beyond of the admissible range, the water system is
flushed automatically for a certain period of time
Switched Off
The humidification function is deactivated via the control software. The hygiene functions (regular
flushing of the water system) remain still active.
Remote Off
The humidification system was stopped via the external enable switch.
Temperature Flush
The water temperature is too high or near the freezing point. The water system is flushed for
a certain time.
Ceramic Wash Over
The optional ceramic wash over is carried out.