45
Operating the Condair DL control software
5.3.5.3 Settings in the "IoT Settings" submenu
The following settings are only required for communication via IoT.
09/01/2021
DL
07:00 pm
Cloud Connection
Channel
Off
Ethernet
IoT Settings
–
Cloud connection
: not yet available!
–
Channel
: not yet available!
5.3.5.4 Settings in the "Modbus Settings" submenu
09/01/2021
DL
07:00 pm
Modbus Protocol
Modbus Address
Parity
Baud Rate
Register Sequence
Modbus/RTU
10
Even
19200
MSR zuerst
Modbus Settings
–
Modbus Protocol
: with this setting you can activate "
Modbus/RTU
" or
"
Modbus/TCP
" communication via a Modbus network or deactivate ("Off")
Modbus communication.
Factory setting:
Modbus/RTU
Options:
Off, Modbus/RTU
or
Modbus/TCP
Important: regarding the setting of the individual Modbus parameters
as well as the wiring of the Condair DL for the Modbus communi-
cation, please observe the instructions in the separate Modbus ad-
dendum manual. This manual can be requested from your Condair
representative.
5.3.5.5 Settings in the "BACnet Settings" submenu
09/01/2021
DL
07:00 pm
BACnet Protocol
Off
BACnet Settings
–
BACnet Protocol
: with this setting you can activate ("BACnet MS/TP" or
"BACnet/IP") or deactivate ("Off") the communication via the integrated
BACnet interfaces.
Factory setting:
Off
Options:
Off
(BACnet interface deactivated)
MS/TP Master
(BACnet MS/TP Master via RS 485
interface)
MS/TP Slave
(BACnet MS/TP Slave via RS 485
interface)
BACnet/IP
(BACnet/IP via RJ45 interface)
Important: regarding the setting of the individual BACnet parameters
as well as the wiring of the Condair DL for the BACnet IP or BACnet
MS/TP communication, please observe the instructions in the sepa-
rate BACnet addendum manual. This manual can be requested from
your Condair representative.