Fault elimination
Code
Message
Information
Warning
Error
Possible causes
Remedy
W50
–––
Out of
Commissioning
This message appears on commissioning if the system or the control unit,
respectively was disconnected from the mains for more than 48 hours. The
system remains blocked for 5 minutes, and then starts automatically with a
flushing cycle.
The control unit was disconnected
from the mains for more than
48 hours.
We recommend disconnecting the wa-
ter supply line from the reverse osmosis
system on the connection of the central
unit and to flush the supply line for
5 minutes into a separate drain. Then,
reconnect the water supply line.
W51
–––
Level Dis. Pump
Level of the disinfectant in the tank is too low. Humidification is further pos-
sible for limited period of time!
Disinfectant in the tank is used up.
Refill disinfectant.
Level sensor is not or not correctly
connected.
Contact your Condair representative.
Level sensor defective.
–––
E54
Leak Monitoring
Leak monitoring has triggered, humidification is stopped!
Water supply line and/or spray circuit
lines to the duct and/or water drain
line leaky.
Check/seal water supply line, spray
circuit lines and water drain line.
Components (tubes, valves, sliver car-
tridge, etc.) in the central unit leaky.
Contact your Condair representative.
Fuse "F2" on the driver board defec-
tive.
W55
E55
Ag-Ion Service
Sliver cartridge is exhausted and must be replaced, humidification is further
possible for limited period of time!
Sliver cartridge not replaced, or silver
cartridge maintenance counter not
reset after sliver cartridge has been
replaced.
Replace sliver cartridge and reset
silver cartridge maintenance counter.
–––
E59
Sensor Nozzle
Pressure
Invalid signal from nozzle pressure sensor PS5!
Pressure sensor PS5 not or not cor-
rectly connected.
Contact your Condair representative.
Pressure sensor PS5 wrong configured.
Pressure sensor PS5 defective.
–––
E62
Nozzle Pressure
Nozzle pressure too high!
Wrong type of nozzle installed.
Contact your Condair representative.
Nozzles clogged.
).
Max. nozzle pressure set too high.
Contact your Condair representative.
Wrong order of spray circuits or spray
valves.
Pressure relief valve on booster
pump set too high.
–––
E63
Ag-Ion Broken
No sufficient current can be built up in the sliver cartridge!
sliver cartridge exhausted or defec-
tive.
Replace silver cartridge (see
).
Electrical supply to sliver cartridge
interrupted.
Contact your Condair representative.
Installed sliver cartridge too small.
Ag board defective.
–––
E64
Ag-Ion Shortcut
Short circuit on sliver cartridge!
sliver cartridge has internal short
circuit due to material defect or due
to exhaustion.
Replace silver cartridge (see
).