64
Fault elimination
BBy pressing on the <Malfunction> button in the home screen the error list shown with all active warning
and error messages. By pressing on the corresponding Warning or Error entry additional information
regarding the malfunction are displayed (see display on the far right).
09/01/2021
DL
07:00 pm
E59 Sensor Nozzle Pre...
E48 Water Temperatu...
0
01-09-2021 - 13:25
0
01-09-2021 - 13:11
1
09/01/2021
DL
07:00 pm
E59 Sensor Nozzle
Pressure
09/01/2021 - 13:25
0
Refer to the malfunction list in
the operation manual for a
description of the fault and
remedial measures.
No valid signal from nozzle/tank
pressure sensor
09/01/2021
DL
07:00 pm
Home
Next Maintenance
1685 hr
Demand
Stopped
0%
1
7.3
Malfunction list
Most operational malfunctions are not caused by faulty equipment but rather by improper installation or
disregard of planning guidelines. Therefore, a complete malfunction diagnosis always involves a thorough
examination of the entire system (e.g., hose connections, humidity control system, etc.).
Note: Remedial measures highlighted in gray in the malfunction list may only be remedied by a Condair
service technician or a service center authorized by Condair. If applicable, contact your Condair repre-
sentative.
Code
Message
Information
Warning
Error
Possible causes
Remedy
W01
–––
Smartcard
No communication with Smartcard.
No Smartcard installed.
Contact your Condair representative.
Smartcard not valid or defective.
–––
E10
Controller Reset
The control unit (Integrated Controller) has been automatically restarted due
to a software problem.
The control unit (Integrated Control-
ler) has been automatically restarted
due to a software problem
Contact your Condair representative
if this problem regularly occurs.
–––
E19
Freeze Protection
Temperature of the supply water is near the freezing point. Temperature
flushing has triggered.
Note: The temperature flushing shall prevent the freezing of the hydraulic
system by the movement of the water. Humidification is still possible.
Temperature of the supply water too low. Check water system. Insulate water
pipes.
Ambient temperature in the area of the
central unit too low.
Place the central unit differently or
protect it from the cold.