Sounder
Number
High Volume
Low Volume
Maximum Consumption, mA (High + Low)
41SAI000
_____ x 16.5 mA
_____ x 5 mA
41SCI000
_____ x 22 mA
_____ x 12 mA
41SAB100
_____ x 10 mA
_____ x 3 mA
41SCB100
_____ x 10 mA
_____ x 3 mA
Total consumption of the sounders in the loop:
Table 2
Calculation of the total consumption of the sounders in the loop with set tone type no. 27:
* NOTE: Sounder / Strobe operating mode (visual and audible parts are enabled in the event of a fire alarm).
Consumption for other operating modes is indicated in the individual installation manuals for each sounder.
41IOM010 – Mini module with 1 monitored input
17/06/2020 14:06
41IOM010
Address
Loop Number
Device Zone
3
2
1
Enabled
New
Device State
More
Remove
OFF
Name
Save
17/06/2020 14:06
Select Input Event
41IOM010
41IOM010-FIRE
41IOM010-GAS
41IOM010-TECHNICAL
The figure shows the settings screen for module 41IOM010.
The module monitors and transmits the input status (ON status, OFF, status) to the panel.
When the button showing the module model (figure 10 h) is pressed, the panel shows a list of options from which to select the
type of message or pre-set action, which is communicated to the panel in the event of its activation:
•
41IOM010 Mini module 1 IN
: no “rapid activation” is associated with the input and it can be used in fire panel
programming logics (virtual inputs / outputs);
•
41IOM010 Fire Alarm*
: if activated, the module functions as a fire detector and generates a “FIRE ALARM” event to the
panel;
•
41IOM010 GAS Alarm
: if activated, the module generates an indication (Gas alarm) on the panel display, useful for
interfacing between conventional gas detectors;
•
41IOM010 Technical Alarm
: if activated, the module generates an indication (Technical alarm warning) on the panel
display.
* Does not conform to EN54-2
After selecting the type of message / event, press “Save”.
Note
: If the setting GAS Alarm or Technical Alarm warning has been selected and saved, pressing MORE in the module menu
will allow you to select whether to Enable or Disable sounder activation when one of these 2 events occurs, by pressing the
button next to the Alarm field.
If there is a fault on the input, it will be partially displayed in the MORE module menu, in the CHANNEL 1 field; faults may be:
•
Open
- The line connected to the input is open, or the double balance resistors are not connected properly on the device
side.
•
Short
- There is a short-circuit in the line connected to the input.
If there are no faults, the following may appear:
•
OFF
– the module is present and the input is not enabled.
•
ON
– the module is present and its input has been enabled.
36