Press “MORE” to access the submenu for alarm and evacuation parameter settings:
•
ALARM SETTINGS
:
◊
Strobe
– only the visual part of the sounders in the loop will be enabled. The panel “SND” output will NOT be enabled.
◊
Sound
- only the audible part of the sounders in the loop will be enabled. The panel “SND” output will be enabled.
◊
Sound / Strobe.
- both audible and visual parts of the sounders in the loop will be enabled. The panel “SND” output will
be enabled.
◊
Individual
– each sounder is activated in accordance with its own individual settings, specified in the “More” menu for
each Sounder device.
•
EVACUATION SETTINGS
:
◊
Strobe
– only the visual part of the sounders in the loop will be enabled. The panel “SND” output will NOT be enabled.
◊
Sound
- only the audible part of the sounders in the loop will be enabled. The panel “SND” output will be enabled.
◊
Sound / Strobe.
- both audible and visual parts of the sounders in the loop will be enabled. The panel “SND” output will
be enabled.
•
ALERT/EVAC VOICE CYCLES
: This function alternates sounders during the Evacuate or Alarm event in progress, by
switching from ON and OFF (strobe only) status according to set times; this means alternating sounders with a voice
evacuation system can be managed directly on site.
◊
OFF
- time interval from 1 to 600 seconds, during the evacuation/alarm the sounders will only work in Strobe mode (for
available models).
◊
ON
- time interval from 1 to 600 seconds, during the evacuation/alarm the sounders will work according to the
“Evacuation Settings” menu - for example, when the option Sound / Strobe is selected, the sounders will sound and flash
at the same time (for available models).
•
POLARITY
– inverts the sounder alternating operating mode from OFF/ON to ON/OFF.
CAUTION: To enable the alternating evacuation cycle function, you need to enter a time other than 0 in both
ON and OFF fields. Otherwise, the alternating feature will not be enabled.
For example: the operating mode is set as “Sound / Strobe” and the alternating times are set as ON: 30 sec. and OFF: 40 sec.
When evacuation is underway at the protected site, system operation according to the evacuation settings will be as follows:
the sounders will ring (evacuate tone) and flash for 30 seconds, then they will flash only for 40 seconds. The cycle will repeat
until the system is Reset or the silencing button is pressed.
•
EVAC ZONES
: on accessing this function a new screen opens allowing the management and enabling of EVAC zones for
the voice evacuation panel connected to the fire protection system via the interface provided
(see paragraph below).