2. INSTALLATION
The fire panel should be installed in a clean, dry place where it will not be subjected to knocks or vibrations. The panel is not
waterproof!
It must be positioned away from sources of heat, and the ambient temperature must be between -5ºС and + 50ºC.
2.1 Removing the front door
To make installing the panel easier, the front door can be removed using the spring-loaded pins inside the panel.
To remove the door, disconnect the flat connection cables originating from the boards inside the panel; use a slotted
screwdriver to lift the pin at the bottom and shift the door outwards so that the pin comes out of its guide hole, then repeat the
same procedure for the pin at the top and unhook the door.
To re-fit the front door, insert the top pin into its hole; use a slotted screwdriver to lift the bottom pin (or do so manually) and
position the door inside the panel frame, so that the second pin also slots into its hole. You will hear it click into place when the
correct position is found. Make sure the door is secure and reconnect the flat cables.