41SCI000 – Sounder with strobe and isolator
17/06/2020 14:06
41SCI000
Address
Loop Number
Device Zone
1
2
1
Enabled
Normal
Device State
More
Remove
OFF
Name
17/06/2020 14:06
Sound/Strobe
High
Mode
Sound Level
Software Revision
ID
2.0
3095402135
0
Sounder Group
The figure shows the settings screen for addressed sounder 41SCI000.
Press “MORE” to access additional settings:
•
Mode
: press the button to change the sounder operating mode; choose between:
◊
Strobe lamp
. - in the event of activation, only the visual part of the sounder is enabled
◊
Sounder
– in the event of activation, only the audible part of the sounder is enabled
◊
Sound/Strobe
– in the event of activation, both visual and audible parts of the sounder are enabled
•
Sound Level
: on pressing the button, the sound level alternates between HIGH and LOW - this setting can be determined
by the total number of sounders connected to the Loop:
◊ High - Set for cases in which the number of sounders connected to a single Loop is ≤ 30.
◊ Low - Set for cases in which the number of sounders connected to a single Loop is between 30 and 60.
•
Sounder Group
: each addressed sounder can belong to a Sounder Group. In the event of a zone alarm, in addition to the
sounders belonging to that zone, the sounder groups associated with that zone will also be activated.
To save any new parameters, press “Save” on the main device screen.
41SAB100 – Base with built-in sounder and isolator
17/06/2020 14:06
41SAB100
Address
Loop Number
Device Zone
14
2
1
Enabled
Normal
Device State
More
Remove
OFF
Name
17/06/2020 14:06
High
Sound Level
Software Revision
ID
2.0
3155660795
0
Sounder Group
The figure shows the settings screen for the base with addressed sounder 41SAB100.
Press “MORE” to access additional settings:
•
Sound Level
: on pressing the button, the sound level alternates between HIGH and LOW - this setting can be determined
by the total number of sounders connected to the Loop:
◊ High - Set for cases in which the number of sounders connected to a single Loop is ≤ 30.
◊ Low - Set for cases in which the number of sounders connected to a single Loop is between 30 and 100.
•
Sounder Group
: each addressed sounder can belong to a Sounder Group. In the event of a zone alarm, in addition to the
sounders belonging to that zone, the sounder groups associated with that zone will also be activated.
To save any new parameters, press “Save” on the main device screen.
Note: the detectors mounted on bases 41SAB100 and 41SCB100 will be assigned another address which is NOT the
same as the base.
34