In System racks: enter the total number of 41 49CCO00X panels in the system (max. 6).
In Rack address: ID address of the EVAC panel on which you are working (from 0 to 4).
Press ESCAPE and SAVE.
For example: if we are using a 41CPE118 panel and one EVAC panel we need to set:
In System racks: 2
In Rack address: 0
If, on the other hand, the system consists of a 41CPE118 panel and 2 EVAC panels, set:
In System racks: 3 (for both Evac panels)
In Rack address: 0 (for the first Evac) and 1 (for the second).
CAUTION:
the numbering of EVAC panels begins at 0 and not 1.
4.7.6 Callpoints mode
In this submenu the installer can choose a mode for the alarm triggered after the flexible element of the manual callpoint button
has been pressed.
Press the active button to change the operating mode, from:
•
Common
- a common alarm is generated, regardless of the zone to which it is linked.
•
Zonal
- an alarm is generated only for the zone with which the manual callpoint button is linked.
17/06/2020 14:06
Callpoints Mode
Common
After completing the changes, press “Save”.
4.7.7 Selecting the language
Here the installer can choose a language from the options available on the system.
To change the language for the 41CPE118 panel menus, simply press the button showing the desired language and save the
change.
4.7.8 Delay (T1)
Here the installer can set a common delay time for the enabling of all outputs (from 0 to 60 seconds).
Used for the first alarm check.
CAUTION: if the zone delay time T2 is set to 0, the common delay time T1 will be ignored.
See APPENDIX E - Operating algorithm “Two alarm status levels”.
72