257
14.2.1.19
Binary input: ManualLdRecon
Related FW
3.0
Description
This input is used for manual reconnection of the last disconnected part of
the load, if the load has dropped below the setpoint
This input works only if automatic reconnection is disabled, i.e. the setpoint
14.2.1.20
Binary input: FaultResButton
Related FW
3.0
Description
This input is used for an external FAULT RESET button mounted on the
switchboard. The function of the input is identical as function of the fault reset
button on the controller front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
14.2.1.21
Binary input: HornResButton
Related FW
3.0
Description
This input is used for an external HORN RESET button mounted on the
switchboard. The function of the input is identical as function of the horn reset
button on the controller front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
14.2.1.22
Binary input: BTBButton
Related FW
3.0
Description
This input is used for an external BTB button mounted on the switchboard.
The function of the input is identical as function of the BTB button on the
controller front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
14.2.1.23
Binary input: GroupLink
Related FW
3.0
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...