This setpoint adjusts the reset (initial) value of the
ExtValue 2
. This initial
value is applied either when the controller is powered-on or when the
ExtValue 2
is reset by the binary input
12.2.11.31
Setpoint: ExtValue3deflt
Group
Force value
Range [units]
-32000 .. 32000 [x]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the reset (initial) value of the
ExtValue 3
. This initial
value is applied either when the controller is powered-on or when the
ExtValue 3
is reset by the binary input
12.2.11.32
Setpoint: ExtValue4deflt
Group
Force value
Range [units]
-32000 .. 32000 [x]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the reset (initial) value of the
ExtValue 4
. This initial
value is applied either when the controller is powered-on or when the
ExtValue 4
is reset by the binary input
12.2.12 Group: Load shedding
12.2.12.1
Setpoint: Ld shed level
Group
Load shedding
Range [units]
Related FW
3.0
Force value
YES
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...