InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
34
4.3
Programming of a controller
4.3.1
Standard programming
For programming GenConfig is used. Select correct connection mode and then select the following
option:
You may use “FW upgrade (from default configuration)” (this will overwrite all of the settings in the
controller with default settings. If you need to upgrade firmware from existing configuration, select “FW
upgrade (from existing confi
guration)”. This function will automatically open wizard which will help you
update the existing configuration to be compatible with the newly selected firmware.
4.3.2
Programming of non-responsive controller
If the controller does not contain valid firmware, new firmware cannot be programmed in the standard
way. This situation can occur if the connection between the PC and the controller was interrupted e.g.
during a previous firmware upgrade. In such case the controller may have a blank display or
connection to InteliVision may not be established and it does not communicate with the PC. The boot-
jumper must be used to get valid firmware into the controller.
Connect proper cable for programming (use RS232 port).
Open GenConfig and select “FW upgrade (default configuration)”
From the following table select FW that is required or click open and browse your files to find
firmware in non-default location
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...