This setpoint is used to adjust the load reserve for stop in relative mode. i.e.
= REL (%) if the reserve set #4 is active. Learn more about
reserves in the chapter
Reserves, minimal running power
.
The currently active reserve set is selected by binary inputs
. If none of these inputs is active the set #1 is selected.
N
OTE
:
The reserve for stop must be always adjusted higher than the reserve for
start.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.22
Setpoint: #NextStrt Del
Group
Pwr Management
Range [units]
0 .. 3600 [s]
Related FW
3.0
Description
This setpoint is used to adjust the delay of starting the next gen-set when the
actual
load reserve
drops below the adjusted reserve for start, but the group
is still not overloaded.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.23
Setpoint: #OverldNext Del
Group
Pwr Management
Range [units]
0 .. 3600 [s]
Related FW
3.0
Description
If the system reserve drops below the start limit for next gen-set the delay
will begin to count down. But if the load raises too quickly it
might happen that the system gets overloaded already before the delay
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...