InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
298
15.2.1.21
Binary output: Common Wrn
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Warning
type
present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm management
for more information.
15.2.1.22
Binary output: Common Fls
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Sensor fail
type
present in the alarm list. The alarm can be in
any state
, i.e. active
unconfirmed, active confirmed or inactive unconfirmed.See the chapter
Alarm
management
for more information.
15.2.1.23
Binary output: Common BOp
Related FW
3.0
Description
This output closes if any "Breaker Open" type alarm appears. The output
opens if no BO type alarm is active (pressing of fault reset button is not
required).
15.2.1.24
Binary output: Common BOR
Related FW
3.0
Description
This output closes if any "Breaker Open with fault reset" type alarm appears.
The output opens if no BOR type alarm is active (pressing of fault reset
button is required).
15.2.1.25
Binary output: Common Al
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Alarm only
type
present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm management
for more information.
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...