InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
253
14.2.1.12
Binary input: AccessLock int
Related FW
3.0
Description
This input forces the controller
built-in
terminal into monitoring mode.
Setpoints changes are disabled.
Using control buttons on the panel is disabled even if the controller is
in MAN mode.
Change of controller mode is disabled.
N
OTE
:
As the IS-NT and IGS-NT-BB do not have built-in terminal, this input is
assigned to the terminal or IntelliVision (display) #1, which is supposed to be
directly attached to the controller or mounted close to it.
14.2.1.13
Binary input: AccessLock D#2
Related FW
3.0
Description
This input forces the external
local
terminal or IntelliVision (display) #2 into
monitoring mode.
N
OTE
:
Local display means that it is connected to dedicated RS485. There is
possibility to connect up to 2 external displays in IG-NT-BB or 1 in IG-NT. It is
possible to connect up to 3 external displays in IS-NT-BB and in IS-NT.
Setpoints changes are disabled.
Using control buttons on the panel is disabled even if the controller is
in MAN mode.
Change of controller mode is disabled.
14.2.1.14
Binary input: AccessLock ext
Related FW
3.0
Description
This input forces all external
remote
terminals into monitoring mode.
Setpoints changes are disabled.
Executing commands is disabled.
Change of controller mode is disabled.
An external remote terminal is any device, which reads and/or writes data
from/into the controller and is connected to the controller via any other
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...