InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
149
Related FW
3.0
Force value
possible
YES
Description
This setpoint determines treshold for busR overvoltage protection. This
protection is evaluated with delay given by setpoint
Protection type is history record.
N
OTE
:
All three phases are checked for busR voltage detection. Maximum out of
those three is used.
For high voltage applications, the BusRNomVph-ph can be used for nominal
voltage setting.
12.2.7.3
Setpoint: BusRight <V
Group
BusR protect
Range [units]
Related FW
3.0
Force value
possible
YES
Description
This setpoint determines treshold for busR undervoltage protection. This
protection is evaluated with delay given by setpoint
Protection type is history record.
N
OTE
:
All three phases are checked for busR voltage detection. Minimum out of
those three is used.
For high voltage applications, the BusRNomVph-ph can be used for nominal
voltage setting.
12.2.7.4
Setpoint: BusRight V del
Group
BusR protect
Range [units]
0.00 .. 600.00 [s]
Related FW
3.0
Description
This setpoint adjusts delay for busR under- (
) and overvoltage
) protections.
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...