InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
154
the master and if it is switched off the next one will take the master role.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
C
AUTION
!
If the controller which is set to MASTER in PriorAutoSwap function is in
, priority autoswapping will not work and no other controller
will assume MASTER role.
12.2.8.3
Setpoint: Priority ctrl
Group
Pwr management
Range [units]
DISABLED, MASTER [-]
Related FW
3.0
Force value
possible
YES
Description
DISABLED
IM-NT does not provide the AutoSwap functions for other
controllers.
MASTER
At least one controller in the logical group has to be
selected as MASTER if some PriorityAuto Swapping
mode is enabled. Only the controller with lowest CAN
address becomes an active master, the other are ignored
by SLAVE controllers. The MASTER controller evaluates
the Priority changing for all other controllers in the group
and sends them the “forced” Priority values.
12.2.8.4
Setpoint: #SysAMFstrtDel
Group
Pwr management
Range [units]
0 .. 600 [s]
Related FW
3.0
Description
System start delay between input
Sys start/stop
closing and start of Power
Management System. When input
Sys start/stop
is controlled by mains
decoupling relay, this setpoint adjusts the delay among the mains failure and
the emergency start of the gen-sets. If the MCB feedback is closed, Power
management is started with 1s delay after the input
Sys start/stop
closing -
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...