InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
306
15.2.1.57
Binary output: LdShed stage 2
Related FW
3.0
Description
This output is used for control of second load group. This group is
disconnected as
second
one when the first group is already disconnected
and the condition for disconnecting of next group is still fulfiled.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
15.2.1.58
Binary output: LdShed stage 3
Related FW
3.0
Description
This output is used for control of third load group. This group is disconnected
as
last
one when the first two groups are already disconnected and the
condition for disconnecting of next group is still fulfiled.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
15.2.1.59
Binary output: CtrlHeartBeat
Related FW
3.0
Description
The output provides alternating signal with rate 500ms active / 500ms
inactive while the controller is
operational
, i.e. it has passed all checks after
startup and no failure was detected.
If the output does not provide the alternating signal it may indicate following:
controller is switched off
or
controller is damaged
or
incorrect/missing firmware and/or application
or
corrupted setpoints
The output is intended for using in wired redundancy systems at the main
controller. Learn more about redundancy in separate chapter
Redundant
controllers
.
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...