InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
141
12.2.6.2
Setpoint: OverldStrtEval
Group
BusL Protect
Range [units]
100 .. 200 [%]
Related FW
3.0
Force value
possible
YES
Description
This setpoint specifies the power level relative to the
, where
the busL overload (IDMT) protection starts to be evaluated. See the setpoint
for more information about the busL overload (IDMT)
protection.
12.2.6.3
Setpoint: 2POvrldStEvDel
Group
BusL Protect
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Description
This setpoint adjusts the reaction time of the busL overload (IDMT) protection
if the load level is 200% of the base level given by the setpoint
The reaction time of the thermal overload protection is not fixed; it depends
on how much is the load above the limit (base level). The higher is the load
the shorter the reaction time will be.