12.2.4.4
Setpoint: BinInp delay 3
Group
ComProtSetting
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the delay #3 which can be assigned to an input
configured as alarm input (protection).
N
OTE
:
Protections configured at a binary inputs can have either fixed 0.5s
evaluation delay or there are three independent delay setpoints and one of
them can be assigned to each particular binary input protection.
12.2.4.5
Setpoint: ForceBlockDel1
Group
ComProtSetting
Range [units]
0.0 .. 60.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as
Force block #1
are started to be
evaluated.
12.2.4.6
Setpoint: ForceBlockDel2
Group
ComProtSetting
Range [units]
0.0 .. 60.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as
Force block #2
are started to be
evaluated.
12.2.4.7
Setpoint: ForceBlockDel3
Group
ComProtSetting
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...