InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
191
Learn more about load shedding in the separate chapter
Load shedding
.
12.2.12.4
Setpoint: Ld recon del
Group
Load shedding
Range [units]
0 .. 600 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used to adjust time period the percentage of the power
transferred through BTB must be below the
reconnection of next load group.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
12.2.12.5
Setpoint: AutoLd recon
Group
Engine Protect
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Force value
possible
YES
Description
This setpoint selects whether the reconnection of the load occurs
automatically when the power transferred through BTB stays below the
must be initiated manually by the input
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
12.2.13 Group: Timer settings
12.2.13.1
Setpoint: Timer channel 1
Group
Timer settings