•
NTP-G252 Install the ONS 15454 M6 Shelf , on page 294
•
NTP-G259 Open and Remove the Standard Door of the ONS 15454 M6
Shelf , on page 327
.
• Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, see the
Electrostatic Discharge and Grounding Guide
for Cisco CPT and Cisco ONS Platforms
•
NTP-G524 Install the Power Modules in the ONS 15454 M6 Shelf , on page
355
Prerequisite Procedures
Required
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
When installing or replacing the unit, the ground connection must always be made first and disconnected
last.
Statement 1046
Warning
Hazardous voltage or energy may be present on DC power terminals. Always replace cover when
terminals are not in service. Be sure uninsulated conductors are not accessible when cover is in place.
Statement 1075
Warning
The battery return connection is treated as DC-I, as defined in Telcordia GR-1089-CORE Issue 5.
Note
The ONS 15454 M6 relies on the protective devices in the building installation to protect against short circuit,
overcurrent, and ground faults. Ensure that the protective devices are properly rated and comply with national
and local codes.
Caution
If the system loses power or both TNC, TNCE, TSC, or TSCE cards are reset and the system is not provisioned
to get the time from a Network Time Protocol/Simple Network Time Protocol (NTP/SNTP) server, you must
reset the ONS 15454 M6 clock. After powering down, the date defaults to January 1, 1970, 00:04:15. To reset
the clock, see the “NTP-G24 Setting Up Node Identification Information” procedure in the
Cisco ONS 15454
DWDM Control Card and Node Configuration Guide
. If you are using the TNC, TNCE, TSC, or TSCE cards,
the system clock will run for up to three hours. In this case, no action would be required.
Note
Procedure
Step 1
Connect the return cables of the power supply to the Earth ground located at the power supply side.
Cisco ONS 15454 Hardware Installation Guide
382
Installing the ONS 15454 M6 Shelf
DLP-G573 Connect Office Power (DC) to the ONS 15454 M6 Shelf (ETSI Only)
Содержание ONS 15454
Страница 2: ... 2019 Cisco Systems Inc All rights reserved ...
Страница 16: ...Cisco ONS 15454 Hardware Installation Guide xvi Contents ...
Страница 28: ...Cisco ONS 15454 Hardware Installation Guide xxviii Preface Preface ...
Страница 36: ...Cisco ONS 15454 Hardware Installation Guide 6 Overview Cisco ONS 15454 M6 Shelf ...
Страница 510: ...Cisco ONS 15454 Hardware Installation Guide 480 Hardware Specifications Dimensions ...