Figure 195: Installing the right vertical air plenum
Step 7
Place the horizontal plenum above the chassis slot in the ETSI cabinet.
Step 8
Install the wing head screws provided with the kit, and tighten to a torque value of 11.5 in-lb (1.3 N-m)..
Figure 196: Installing the horizontal air plenum above the vertical plenums
Step 9
Install the standard brackets on both sides of the chassis in front position. See
Brackets on the ONS 15454 M6 Shelf for ETSI Rack Configuration, on page 304
.
Step 10
Check the length between the top and bottom horizontal air plenums where the chassis will be installed. The
length must be not less than 10.5 inches (267 mm). If the length is less, adjust the position of the top horizontal
plenum.
Cisco ONS 15454 Hardware Installation Guide
292
Installing the ONS 15454 M6 Shelf
DLP-G769 Install Air Plenum for ONS 15454 M6 Shelf in ETSI Configuration
Содержание ONS 15454
Страница 2: ... 2019 Cisco Systems Inc All rights reserved ...
Страница 16: ...Cisco ONS 15454 Hardware Installation Guide xvi Contents ...
Страница 28: ...Cisco ONS 15454 Hardware Installation Guide xxviii Preface Preface ...
Страница 36: ...Cisco ONS 15454 Hardware Installation Guide 6 Overview Cisco ONS 15454 M6 Shelf ...
Страница 510: ...Cisco ONS 15454 Hardware Installation Guide 480 Hardware Specifications Dimensions ...