July 2010
Chapter 2 Alarm Troubleshooting
2.6.49 EQPT-HITEMP
2.6.49 EQPT-HITEMP
Default Severity: Minor (MN), Non-Service-Affecting (NSA)
Logical Object: EQPT
The Equipment Failure High Temperature alarm occurs when the TSC card, SSXC card, or traffic
(STM-N) card internal temperature exceeds 185 degrees Fahrenheit (85 degrees Celsius).
Clear the EQPT-HITEMP Alarm
Step 1
Ensure that the room temperature is not abnormally high.
Step 2
If the room temperature is not the cause of the alarm, ensure that filler modules are installed in the
ONS 15600 SDH empty slots. Filler modules help airflow.
Caution
Always use the supplied electrostatic discharge wristband when working with a powered
ONS 15600 SDH. Plug the wristband cable into the ESD jack located on the lower-right edge of the shelf
assembly.
Step 3
If the
“FAN-DEGRADE” alarm on page 2-56
or the
accompanies the
alarm, complete the
“Clear the FAN-FAIL Alarm” procedure on page 2-57
Step 4
If the alarm does not clear, check the condition of the air filter to see if it needs cleaning or replacement.
Replace the air filter using the procedure located in the “Maintain the Node” chapter in the
Cisco ONS 15600 SDH Procedure Guide
as needed.
Step 5
If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1 800 553-2447).
2.6.50 EQPT-PIM-PPM
Default Severity: Critical (CR), Service-Affecting (SA)
Logical Object: PPM
The EQPT alarm for an SFP (PPM) is raised when a 4PIO (PIM) is reporting low electrical amplitude
from an SFP (PPM). If this symptom shows up from multiple SFPs (PPMs) then the alarm should be
against the 4PIO (PIM). Otherwise the alarm will be against the SFP (PPM) creating the problem.
Clear the EQPT-PIM-PPM Alarm
Step 1
Move any traffic away from the affected SFP (PPM), using guidelines and instructions in the “Maintain
the Node” chapter in the
Cisco ONS 15600 SDH Procedure Guide
, then replace the alarmed SFP (PPM)
module using instructions in that guide.
Step 2
If the alarm does not clear, move any traffic away from the affected 4PIO (PIM), using the instructions
in the “Install Cards and Fiber-Optic Cable” chapter in the
Cisco ONS 15600 SDH Procedure Guide
, and
replace the 4PIO (PIM).
Содержание Cisco ONS 15600 SDH
Страница 18: ...Contents xviii Cisco ONS 15600 SDH Troubleshooting Guide R8 0 July 2010 ...
Страница 20: ...Figures xx Cisco ONS 15600 SDH Troubleshooting Guide R8 0 July 2010 ...
Страница 30: ...xxx Cisco ONS 15600 SDH Troubleshooting Guide R8 0 July 2010 About this Guide ...
Страница 256: ...3 8 Cisco ONS 15600 SDH Troubleshooting Guide R8 0 July 2010 Chapter 3 Transient Conditions 3 3 28 WKSWPR ...
Страница 306: ...4 50 Cisco ONS 15600 SDH Troubleshooting Guide R8 0 July 2010 Chapter 4 Error Messages ...
Страница 318: ...Index IN 12 Cisco ONS 15600 SDH Troubleshooting Guide R8 0 July 2010 ...