C/10: Capacity (Ah),
Battery capacity during discharge C/10.
C/10: V disch (V),
Cut-off voltage during discharge C/10.
Cell Voltage: Float,
Floating voltage of each cell.
Cell Voltage: Absorption,
Absorption voltage of each cell.
Cell Voltage: Equ,
Balancing voltage of each cell.
Note:
These parameters appear in the battery datasheet.
Note:
The default values correspond to OPzV batteries. If you do not know the values and your
battery is compatible with this technology, you can use the default values.
It is
strongly advised
to enter the battery capacity under different discharge conditions:
<
C/10: Time (h),
discharge time.
<
C/10: Capacity (Ah),
Capacity of the battery during discharge with a discharge time of
less than 10 hours.
< C/10: V disch (V),
Cut-off voltage during discharge for a discharge time of less than 10
hours.
>
C/10: Time (h),
discharge time.
>
C/10: Capacity (Ah),
Capacity of the battery during discharge with a discharge time of
more than 10 hours.
> C/10: V disch (V),
Cut-off voltage during discharge for a discharge time of more than 10
hours.
Note:
If you are not going to enter this information, set the
Time
variable to 0 and all other pa
-
rameters will be disabled.
This information is used by the internal BMS to estimate the state of charge of the battery.
Therefore, the more information is available, the more reliable the calculation of the
SOC
will
be.
If a Li-Ion battery has been selected with an external BMS, when you click on
Next
the screen
in
Figure 47
is displayed, where you have to enter the number of battery modules connected in
parallel.
Figure 47: Battery setup: number of modules�