5.4.- AC OUTPUT CONNECTION
Figure 12: AC output connection�
Hybrid inverter allow the connection of loads to the AC Output terminal. This output is powered
by Ac-In. In case of Ac-In failure, it is powered either by battery or solar power.
Connection is done by means of a 3-pole Wieland Gesis RST25i pluggable connector.
Recommended wire section is 6mm
2
. Select wire insulation type depending on installation en-
vironmental conditions and local regulations.
It is mandatory to use an external type A RCB, rated for 25A 30mA. As well, it is mandatory to
use a 25A circuit breaker.
Please, follow local regulations regarding this type of installations.
Risk of death due to dangerous voltages�
Do not connect the grid to the AC Output connector�
If the grid is connected to the AC Output connector, the anti-islanding protection
will not be ensured and the AC Output connector will not protect the user from the
dangerous voltages.
During off-grid working mode, the neutral is automatically connected to earth. Take this into
account to ensure the inverter meet you local regulations.
Figure 13: Connect the AC output�
20
CirPower Hyb 4k-48
Instruction Manual