Table 24 (Continuation): Alarm messages description�
Alarms
AC Output overload
Description
10
Vac output min
warnings were generated over a period of 1 hour while oper-
ating in the isolated from grid mode. Requires manual rearming.
Actions
Reduces the direct load and/or battery charging consumption.
Error xxxxxx
Description
Internal error.
Actions
Contact Technical Service, and indicate the error code.
Error Comms DSP1/2
Description
Internal communications error.
Actions
Restart the device. If the error persists, contact Technical Service and indicate the
error code.
Error Comms Ext� BMS
Description
Error communicating with the external battery controller.
Actions
The device is unable to ensure the safety of the battery without this communi-
cation and it shuts down. Check the configuration and connections and see the
battery’s documentation.
Error diff Vbat / Error num cells
Description
High voltage difference between the battery voltage read by the device and that
reported by the battery’s BMS.
Actions
Check the connections and configuration.
Error temp max/min
Description
The temperature reported by the battery’s BMS exceeds the safety limits.
Actions
Check communication with the battery
Ext BMS fault
Description
The battery’s external controller has reported an error.
Actions
View the error on the battery’s value display screen. See the battery’s documen-
tation.
8�4�2�- WARNINGS
Press the
button to access the warnings screen.
The screen,
Figure 80
, shows the active warnings.