Tabla 25 (continuation): Warnings messages description�
Warnings
Inv-2000: High network voltage
Description
Grid voltage too high.
Inv-4000:
Awaiting mains connection
Description
Depending on the grid connection standard, the inverter will wait several minutes
to connect to the grid. The grid must meet some voltage and frequency limits.
Inv-8000:
Island detection
Description
There is no grid voltage, or it is out of limits
Inv-1000000: Error communicating with external device
Descripción
A connected external device (BMS, analyser) is not responding to the device’s
requests. Check the configuration and connections.
PV-1:
Solar Conv� Communication error
Description
If this warning remains activated, reboot the system. Contact Technical Service.
PV-2: Minimum PV voltage
Description
The photovoltaic voltage is too low. There might not be enough sunlight or the PV
switch is open.
PV-4: Not enough sunlight
Description
PV voltage/power is too low. Not enough sunlight, or the PV switch is opened.
It can remain active for a few minutes after recovering the voltage/photovoltaic
power (see
“9.2.2.3.- Photovoltaic waiting time”)
PV-8:
Deactivated solar converter
Description
Internal circuitry stopped to save energy
PV-10: High PV voltage
Description
The photovoltaic voltage exceeds the top start-up limit (680V).
Check the photovoltaic energy installation.
PV-20: Calibration error
Description
If it does not disappear, restart the device. Contact the Technical Assistance Ser-
vice.
Chg-1:
Disconnected battery
Description
Battery disconnected. Check connection, or replace batery.
Chg-2 :
Battery deep discharge
Description
Batery deep discharge. Risk to damage battery. Charge battery inmediatly. Check
battery status. Check connections to battery
Chg-8: Vbat max
Description
Battery overvoltage. Check the condition of the battery. Check the battery connec-
tions
Chg-10: Vbus min
Description
A message indicating the incident is usually displayed.
Chg-20:
Vbus max
Description
If this warning remains activated, reboot the system. Contact Technical Service
Chg-40:
Temp battery max
Description
Battery temperature too high. Cool down batteries.
Chg-80: Charger Heatsink 1 temp max
Description
Charger heatsink temperature high
Chg-100:
Charger Heatsink 2 temp max
Description
Charger heatsink temperature high
81
Instruction Manual
CirPower Hyb 4k-48