Table 32:Modbus memory map: Display variables (3)
Solar panel variables
Display variable
Address
Units
Solar panel voltage
0294
V (1 decimal)
Solar panel current
0295
A (2 decimals)
Solar panel power
0296
W
Solar converter energy
0297
kWh (2 decimals)
Table 33:Modbus memory map: Display variables (4)
Solar panel variables
Display variable
Address
Response
Warning / Alarm message
0299
Alarm and/or warning codes of the solar conver-
ter described in
sections 8�4�1�
and
8�4�2�
Output saturation
029A
Power limitation indication of the solar converter
Table 34:Modbus memory map: Display variables (5)
Battery variables
Display variable
Address
Units
Battery charger software version
02BC
-
SOC
02BD
%
Battery level
02BE
4:
Battery full -
3:
Battery OK
2:
Low battery -
1:
Battery empty
Battery voltage
02BF
V (2 decimals)
Battery current
02C0
A (2 decimals)
Battery power
02C1
W
Battery temperature
02C2
ºC (1 decimal)
Temperature of the heatsink, battery charger 1
02C3
ºC (1 decimal)
Temperature of the heatsink, battery charger 2
02C4
ºC (1 decimal)
DC Bus voltage of the battery charger
02C5
V (1 decimal)
DC Bus current of the battery charger
02C6
A (2 decimals)
DC Bus power of the battery charger
02C7
W
Charging energy of the battery charger
02C8
kWh
Discharge energy of the battery charger
02C9
kWh
Battery charge level
02CA
Ah
Table 35:Modbus memory map: Display variables (6)
Battery variables
Display variable
Address
Response
Warning / Alarm message
02CD - 02CE Alarm and/or warning codes of the battery charger des-
cribed in sections
8�4�1�
and
8�4�2�
Battery capacity and efficiency
02CF
0xAABB
AA:
Battery efficiency, expressed as a %
BB :
Reduction of the battery capacity in relation to the
nominal value, expressed as a %
Output saturation
02D0
Any value in this log indicates that the power of the
battery charger is being limited.