Tabla 29 (continuation):Modbus memory map: Configuration variables (Solar converter)�
Solar converter
Configuration variable
Address
Valid data margin
Default value
Minimum stop current
006A
0�1- 1�0 A
0.3
Minimum injection voltage
00A5
170 - 250 V
170
Photovoltaic waiting time
00A8
1 - 120 min
15
10�1�2�2� Display variables
Table 30:Modbus memory map: Display variables (1)
Inverter variables
Display variable
Address
Units
Inverter software version
0258
-
Network frequency
0259
Hz (2 decimals)
Network voltage L1
025A
V (1 decimal)
Network Current L1
025B
A (2 decimals)
Active network current L1
025C
W
Reactive network current L1
025D
Var
Apparent network power L1
025E
VA
Network cos φ L1
025F
-
Energy injected into the Grid
026C
kWh (2 decimals)
Energy consumed from the Grid
026D
kWh (2 decimals)
Inverter frequency
026E
Hz (2 decimals)
Inverter voltage L1
026F
V (1 decimal)
Inverter current L1
0270
A (2 decimals)
Active power Inverter L1
0271
W
(< 0 Consumes from the grid > 0, Generates)
Reactive power Inverter L1
0272
Var
Apparent power Inverter L1
0273
VA
(< 0 Consumes from the grid, > 0 Generates)
Energy generated by the inverter
027E
kWh (2 decimals)
Energy consumed by the inverter
027F
kWh (2 decimals)
Heatsink temperature in the inverter IGBT area
0280
ºC
DC bus voltage (measured by the inverter)
0281
V (1 decimal)
DC bus current (measured by the inverter)
0282
A (2 decimals)
DC bus power (measured by the inverter)
0283
W
Power available to the inverter for local isolated
loads
028E
W
Table 31:Modbus memory map: Display variables (2)
Inverter variables
Display variable
Address
Response
Status of the anti-islanding relay
0284
1:
Open -
2:
Closed
Warning / Alarm message
0285 - 0286
Alarm and/or warning codes of the inverter
described in
sections 8�4�1
. and
8�4�2
.
Saturation at the output
0287
Inverter power limitation indication
94
CirPower Hyb 4k-48
Instruction Manual