Installation
34
Rev. 10/17
Brave 30 ES - Brave 60 ES - Brave 90 ES
4.5.5 Connecting the python
Connect the python to the dispensing tower (not included) with the soda recirculation line.
When positioning the python, keep it away from heat sources, particularly tight bends, or any
point where it may get crushed.
The tubes in the python are marked with numbers (or different colours) to facilitate the
connection between the coils and the respective dispensing valves.
The thickness of the python insulation depends on the environmental temperature and the degree of
humidity.
Refer to the tables below.
ENVIRONMENTAL TEMPERATURE OF 30°
ENVIRONMENTAL TEMPERATURE OF 23°
INSULATING
THICKNESS (mm)
HEAT ACQUIRED BY THE DRINK (W/25m)
ENV.TEMP. / DRINK AT 32°C ENV.TEMP. / DRINK AT 43°C
9
388
521
13
288
387
19
197
265
25
141
189
32
97
131
NOMINAL
INSULATING THICKNESS
(mm)
RELATIVE HUMIDITY
60%
70%
75%
80%
85%
9
13
19
NOMINAL
INSULATING THICKNESS
(mm)
RELATIVE HUMIDITY
60%
70%
75%
80%
85%
9
13
19
BR0320
SODA RECIRCULATION
SYRUP TUBES
SYRUP TUBES
INSULATING
THICKNESS