
95
Table 114 — Alert and Alarm Codes (cont)
LEGEND
For 48/50A2,A3,A4,A5 units:
• Compressor internal overload protector is open. Internal
overload protectors are used in the Copeland compressors in
all units except size 60 ton units with voltages of 208/230-v,
380-v, and 575-v.
• Compressor external overload protector (Kriwan module)
has activated. The Copeland compressors in size 60 ton
units with voltages of 208/230-v, 380-v, and 575-v use
external overload protector modules that are mounted in the
compressor wiring junction box. Temperature sensors
embedded in the compressor motor windings are the inputs
to the module. The module is powered with 120 vac from
the units main control box. The module output is a normally
closed contact that is wired in series with the compressor
contactor coil. In a compressor motor overload condition,
the contact opens de-energizing the compressor contactor.
• Circuit breaker trip. The compressors are protected from
short circuit by a breaker in the control box. On the 020-050
size units there is one breaker per two compressors and on
the 060 size units there is one breaker per compressor.
• Wiring Error. A wiring error might not allow the compres-
sor to start.
To check out alerts 051, 052, 055 and 056:
1. Turn on the compressor in question using Service Test
mode. If the compressor does not start, then most likely
the problem is one of the following: HPS open, open
internal protection, circuit breaker trip, incorrect safety
wiring, or incorrect compressor wiring.
2. If the compressor does start verify it is rotating in the
correct direction.
ALARM
OR
ALERT
NUMBER
DESCRIPTION
ACTION TAKEN BY CONTROL
RESET
METHOD
PROBABLE CAUSE
T300
Space Temperature Below Limit
Stop cooling, but continue
to heat
Automatic
Outdoor dampers stuck, no load
T301
Space Temperature Above Limit
Stop heating, but continue
to cool
Automatic
High load, dampers open
T302
Supply Temperature Below Limit
Continue to run unit
Automatic
Dampers open, check configuration
setpoint
T303
Supply Temperature Above Limit
Continue to run unit
Automatic
Dampers open, check configuration
setpoint
T304
Return Temperature Below Limit
Continue to run unit
Automatic
Dampers open, check configuration
setpoint
T305
Return Temperature Above Limit
Continue to run unit
Automatic
Dampers open, check configuration
setpoint
T308
Return Air Relative Humidity Below Limit
Alert
Automatic
Configuration error, or sensor error
T309
Return Air Relative Humidity Above Limit
Continue to run unit
Automatic
Dampers open, check configuration
setpoint
T310
Supply Duct Static Pressure Below Limit
Continue to run unit
Automatic
VFD problem, broken fan belt
T311
Supply Duct Static Pressure Above Limit
Continue to run unit
Automatic
VFD problem, broken fan belt
T312
Building Static Pressure Below Limit
Continue to run unit
Automatic
Exhaust issues, check setpoint
T313
Building Static Pressure Above Limit
Continue to run unit
Automatic
Exhaust issues, check setpoint
T314
IAQ Above Limit
Continue to run unit
Automatic
Damper or IAQ control issues
A404
Fire Shut Down Emergency Mode (fire-smoke)
Unit Shutdown
Automatic
Smoke detector switch or external
switch
A405
Evacuation Emergency Mode
Run power exhaust
Automatic
Special fire mode control
A406
Pressurization Emergency Mode
Run supply fan
Automatic
Special fire mode control
A407
Smoke Purge Emergency Mode
Run supply and exhaust fans
Automatic
Special fire mode control
T408
Dirty Air Filter
Continue to run unit
Automatic
Dirty filter, switch setting
A409
Supply Fan Status Failure
Stop unit
Automatic
Fan drive failure
T409
Supply Fan Status Failure
Continue to run unit
Automatic
Fan drive failure, or sensor failure
T414
Loss of Communication with the Belimo Actuator
Close economizer
Automatic
Calibrate economizer, economizer
failure, wiring
T414
Belimo Actuator Direction Error
Close economizer
Automatic
Motor direction switch wrong, wiring
T414
Belimo Actuator Failure
Attempt to close economizer
Automatic
Motor failure
T414
Belimo Actuator Jammed
Close economizer
Automatic
Obstruction in damper
T414
Belimo Actuator Range Error
Close economizer
Automatic
Calibrate economizer
T420
R-W1 Jumper Must Be Installed to Run Heat in Service
Test
No heat
Automatic
Add red wire jumpers
T421
Thermostat Y2 Input ON without Y1 ON
Assume Y2 is Y1
Automatic
Thermostat wiring error
T422
Thermostat W2 Input ON without W1 ON
Assume W2 is W1
Automatic
Thermostat wiring error
T423
Thermostat Y and W Inputs ON
Alert
Automatic
Thermostat issues
T424
Thermostat G Input OFF on a Call for Cooling
Turn fan on
Automatic
Thermostat or wiring issues
T500
Current Sensor Board Failure - A1
Stop compressor A1
Automatic
Faulty board or wiring
T501
Current Sensor Board Failure - A2
Stop compressor A2
Automatic
Faulty board or wiring
T502
Current Sensor Board Failure - B1
Stop compressor B1
Automatic
Faulty board or wiring
T503
Current Sensor Board Failure - B2
Stop compressor B2
Automatic
Faulty board or wiring
A700
Supply Air Temperature Sensor Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
T701
Staged Gas Thermistor 1 Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
T702
Staged Gas Thermistor 2 Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
T703
Staged Gas Thermistor 3 Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
A704
Staged Gas Leaving Air Temp Sum Total Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
T705
Limit Switch Thermistor Failure
Stop staged gas heat
Automatic
Faulty switch or wiring
Axxx —
Alarm
Pxxx —
Pre-Alert
CEM —
Controls Expansion module
Txxx —
Alert
IAQ
—
Indoor Air Quality
TXV
—
Thermostatic Expansion Valve
OAT
—
Outdoor Air Temperature
VFD
—
Variable Frequency Drive
IMPORTANT: Prolonged operation in the wrong direction
can damage the compressor. Correct rotation can be veri-
fied by a gage set and looking for a differential pressure
rise on start-up.
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...