Table 79 — Economizer Configuration Table
Custom Psychrometric Curves — Refer to the psychrometric
chart and the standard Honeywell A-D curves in Fig. 10. The
curves start from the bottom and rise vertically, angle to the left
and then fold over. This corresponds to the limits imposed by
dry bulb changeover, outdoor enthalpy changeover and
outdoor dewpoint limiting respectively. Therefore, it is now
possible to create any curve desired with the addition of one
outdoor relative humidity sensor and the options for change-
over now available. See Fig. 11 for an example of a custom
curve constructed on a psychrometric chart.
UNOCCUPIED ECONOMIZER FREE COOLING — This
Free Cooling function is used to start the supply fan and use
the economizer to bring in outside air when the outside
temperature is cool enough to pre-cool the space. This is done
to delay the need for mechanical cooling when the system
enters the occupied period. This function requires the use of a
space temperature sensor.
When configured, the economizer will modulate during an
unoccupied period and attempt to maintain space temperature
to the occupied cooling set point. Once the need for cooling has
been satisfied during this cycle, the fan will be stopped.
Configuring the economizer for Unoccupied Economizer
Free Cooling is done in the
UEFC
group. There are three
configuration options,
FC.CF
,
FC.TM
and
FC.LO
.
Unoccupied Economizer Free Cooling Configuration
(
FC.CF
) — This option is used to configure the type of unoc-
cupied economizer free cooling control that is desired.
0 = disable unoccupied economizer free cooling
1 = perform unoccupied economizer free cooling as available
during the entire unoccupied period.
2 = perform unoccupied economizer free cooling as available,
FC.TM
minutes before the next occupied period.
Unoccupied Economizer Free Cooling Time Configuration
(
FC.TM
) — This option is a configurable time period, prior to
the next occupied period, that the control will allow unoccu-
pied economizer free cooling to operate. This option is only
applicable when
FC.CF
= 2.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
EC.EN
Economizer Installed?
Yes/No
ECON_ENA
Yes
EC.MN
Economizer Min.Position
0 - 100
%
ECONOMIN
5
EC.MX
Economizer Max.Position
0 - 100
%
ECONOMAX
98
E.TRM
Economzr Trim For SumZ ?
Yes/No
ECONTRIM
Yes
E.SEL
Econ ChangeOver Select
0 - 3
ECON_SEL
0
OA.E.C
OA Enthalpy ChgOvr Selct
1 - 5
OAEC_SEL
4
OA.EN
Outdr.Enth Compare Value
18 - 28
OAEN_CFG
24
OAT.L
High OAT Lockout Temp
-40 - 120
dF
OAT_LOCK
60
O.DEW
OA Dewpoint Temp Limit
50 - 62
dF
OADEWCFG
55
ORH.S
Outside Air RH Sensor
Enable/Disable
OARHSENS
Disable
E.TYP
Economizer Control Type
1 - 3
ECON_CTL
1
EC.SW
Economizer Switch Config
0 - 2
ECOSWCFG
0
E.CFG
ECON.OPERATION CONFIGS
E.P.GN
Economizer Prop.Gain
0.7 - 3.0
EC_PGAIN
1
E.RNG
Economizer Range Adjust
0.5 - 5
^F
EC_RANGE
2.5
E.SPD
Economizer Speed Adjust
0.1 - 10
EC_SPEED
0.75
E.DBD
Economizer Deadband
0.1 - 2
^F
EC_DBAND
0.5
UEFC
UNOCC.ECON.FREE COOLING
FC.CF
Unoc Econ Free Cool Cfg
0-2
UEFC_CFG
0
FC.TM
Unoc Econ Free Cool Time
0 - 720
min
UEFCTIME
120
FC.L.O
Un.Ec.Free Cool OAT Lock
40 - 70
dF
UEFCNTLO
50
Fig. 11 — Custom Changeover Curve Example
A48-7731
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...