38
out a LOW COOL or a HIGH COOL mode and maintain a
low or high cool supply air set point.
•
C.TYP
= 6
(SPT-2 STG)
This configuration will force the control to monitor the
space temperature sensor to make a determination of mode
and allow two stages of cooling.
MACHINE DEPENDENT CONFIGURATIONS — Some
configurations are linked to the physical unit and must not be
changed. The configurations are provided in case a field re-
placement of a board occurs and the settings are not preserved
by the download process of the new software. The following
configurations apply to all machine control types (
C.TYP
) ex-
cept 4 and 6. These configurations are located at the local dis-
play under
Configuration
UNIT
.
See Table 44.
Table 44 — Machine Dependent Configurations
*Dependent on unit.
Unit Size (
SIZE
) — There are several unit sizes (tons) for the
A Series control. Make sure this configuration matches the size
called out by the model number of the unit. This is important as
the cooling stage tables are directly determined based on this
configuration.
Refrigerant Type (
RFG.T
) — This configuration specifies the
type of refrigerant used in the unit. Configuration
RFG.T
is set
to 0 if the refrigerant used is R-22. Configuration
RFG.T
is set
to 1 if the refrigerant used is R-410A. Make sure this configu-
ration matches the refrigerant called out by the model number
of the unit.
Condenser Type (
CND.T
) — This configuration specifies the
type of condenser installed in the unit. Configuration
CND.T
is
set to 0 if the condenser is a round tube, plate fin coil (RTPF).
Configuration
CND.T
is set to 1 if the condenser is a micro-
channel heat exchanger coil (MCHX). Make sure this configu-
ration matches the condenser type called out by the model
number of the unit.
SET POINTS — The set points for both cooling and heating
are located at the local display under
Setpoints
.
See Table 45.
SUPPLY AIR RESET CONFIGURATION — Supply Air
Reset can be used to modify the current cooling supply air set
point. Supply Air Reset is applicable to control types,
C.TYP
=
1,2,3, and 5. The configurations for reset can be found at the
local display under
Configuration
EDT.R.
See Table 46.
EDT Reset Configuration (
RS.CF
) — This configuration ap-
plies to several machine control types (
Configuration
UNIT
C.TYP
=
1,2,3, and 5).
• 0 = NO RESET
No supply air reset is in effect
• 1 = SPT RESET
Space temperature will be used as the reset control variable
along with both
RTIO
and
LIMT
in the calculation of the
final amount of reset to be applied (
Inputs
RSET
SA.S.R
).
• 2 = RAT RESET
Return-air temperature will be used as the reset control vari-
able along with both
RTIO
and
LIMT
in the calculation of
the final amount of reset to be applied (
Inputs
RSET
SA.S.R
).
• 3 = 3RD PARTY RESET
The reset value is determined by a 4 to 20 mA third party
input. An input of 4 mA would correspond to 0º F reset. An
input of 20 mA would correspond to 20º F reset. Configur-
ing the control for this option will cause
RES.S
to become
enabled automatically with the CEM board. To avoid
alarms make sure the CEM board and third party input are
connected first before enabling this option.
Reset Ratio (
RTIO
) — This configuration is used when
RS.CF
is set to 1 or 2. For every degree that the controlling
temperature (space/return) falls below the occupied cooling set
point (
OCSP
), the calculated value of the supply air reset will
rise by the number of degrees as specified by this parameter.
Reset Limit (
LIMT
) — This configuration is used when
RS.CF
is set to 1 or 2. This configuration places a clamp on the
amount of supply air reset that can be applied.
EDT 4-20 mA Reset Input (
RES.S
) — This configuration is
automatically enabled when
Configuration
EDT.R
RS.CF
is set to 3 (third party reset).
COOLING CONFIGURATION — Relevant configurations for
mechanical cooling are located at the local display under
Configuration
COOL
.
See Table 47.
Table 45 — Setpoints
Table 46 — Supply Air Reset Configuration
ITEM
EXPANSION
RANGE
CCN
POINT
DEFAULTS
UNIT
UNIT CONFIGURATION
SIZE
Unit Size (20-60)
20-60
UNITSIZE
*
RFG.T
REFRIG
0-1
REFRIG_T
*
CND.T
CND HX TYP
0-1
COILTYPE
*
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
OHSP
Occupied Heat Setpoint
40-99
dF
OHSP
68
OCSP
Occupied Cool Setpoint
40-99
dF
OCSP
75
UHSP
Unoccupied Heat Setpoint
40-99
dF
UHSP
55
UCSP
Unoccupied Cool Setpoint
40-99
dF
UCSP
90
GAP
Heat-Cool Setpoint Gap
2-10
^F
HCSP_GAP
5
V.C.ON
VAV Occ. Cool On Delta
0-25
^F
VAVOCON
3.5
V.C.OF
VAV Occ. Cool Off Delta
1-25
^F
VAVOCOFF
2
SASP
Supply Air Setpoint
45-75
dF
SASP
55
SA.HI
Supply Air Setpoint Hi
45-75
dF
SASP_HI
55
SA.LO
Supply Air Setpoint Lo
45-75
dF
SASP_LO
60
SA.HT
Heating Supply Air Setpt
90-145
dF
SASPHEAT
85
T.PRG
Tempering Purge SASP
–20-80
dF
TEMPPURG
50
T.CL
Tempering in Cool SASP
5-75
dF
TEMPCOOL
5
T.V.OC
Tempering Vent Occ SASP
–20-80
dF
TEMPVOCC
65
T.V.UN
Tempering Vent Unocc. SASP
–20-80
dF
TEMPVUNC
50
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
EDT.R
EVAP.DISCHRGE TEMP RESET
RS.CF
EDT Reset Configuration
0 - 3
EDRSTCFG
0
RTIO
Reset Ratio
0 - 10
RTIO
2
LIMT
Reset Limit
0 - 20
^F
LIMT
10
RES.S
EDT 4-20 ma Reset Input
Enable/Disable
EDTRSENS
Disable
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...