28
Variable Air Volume Units Using Return Air
Sensor or Space Temperature Sensor —
To con-
figure the unit, perform the following:
1. The type of control is configured under
Configuration
UNIT
C.TYP
. Set
C.TYP
to 1 (VAV-RAT) for return
air sensor. Set
C.TYP
to 2 (VAV-SPT) for space tempera-
ture sensor.
NOTE: For VAV with a space sensor (VAV-SPT), under
Configuration
UNIT
SENS
SPT.S
, enable the
space sensor by setting
SPT.S
to ENBL.
2. Install jumpers between R-W2 and W2-W1 on TB4 in
the control box.
3. The space temperature set points and the supply air set
points are configured under the Setpoints menu. The
heating and cooling set points must be configured. See
the Heating Control and Cooling Control sections for
further description on these configurations. Configure the
following set points:
4. To program time schedules, make sure
SCH.N
=1 under
Configuration
CCN
SC.OV
SCH.N
to configure
the control to use local schedules.
5. Under the
Timeclock
SCH.L
submenu, enter the de-
sired schedule. See Time Clock Configuration section on
page 75 for further description of these configurations.
6. Under
Configuration
SP
SP.SP
, the supply duct Stat-
ic Pressure Setpoint should be configured.
7. If supply air temperature reset is desired, under the
Configuration
EDT.R
submenu, the following set
points should be configured:
NOTE: Configure either
RTIO
and
LIMT
or
RES.S
. All three
are not used.
8. See the Economizer Options section on this page for ad-
ditional economizer option configurations.
9. See the Exhaust Options section on page 29 for additional
exhaust option configurations.
Multi-Stage Constant Volume Units with
Mechanical Thermostat —
To configure the unit, per-
form the following:
1. Under
Configuration
UNIT
C.TYP
, set
C.TYP
to 3
(TSTAT MULTI).
2. Remove jumpers from R-W2 and W2-W1 on TB4 in the
control box. Connect thermostat to TB4.
3. Under the
Setpoints
menu, set the following
configurations:
4. See the Economizer Options section on this page for ad-
ditional economizer option configurations.
5. See the Exhaust Options section on page 29 for additional
exhaust option configurations.
Multi-Stage Constant Volume Units with
Space Sensor —
To configure the unit, perform the
following:
1. Under
Configuration
UNIT
C.TYP
, set
C.TYP
to 5
(SPT MULTI).
2. Install jumpers between R-W2 and W2-W1 on TB4 in
the control box.
3. Under the
Setpoints
menu, the following configurations
should be set:
4. The degrees of demand from the space temperature set
points are configured under the
Configuration
D.LV.T
submenu. See the Heating Control and Cooling Control
sections for further description on these configurations.
Configure the following set points:
5. Under
Configuration
UNIT
SENS
SPT.S
, enable
the space sensor by setting
SPT.S
to ENBL.
6. Under
Configuration
UNIT
CV.FN
, set
CV.FN
to 1
for continuous fan or 0 for automatic fan.
7. To program time schedules, set
SCH.N
=1 under
Config-
uration
CCN
SC.OV
SCH.N
to configure the con-
trol to use local schedules.
8. Under the
Timeclock
SCH.L
submenu, enter the de-
sired schedule. See Time Clock Configuration section on
page 75 for further description of these configurations.
9. See the Economizer Options section below for additional
economizer option configurations.
10. See the Exhaust Options section on page 29 for additional
exhaust option configurations.
Economizer Options —
Under the
Configuration
ECON
submenu, the following set points may be configured:
Configuration
ECON
EC.MN
should always be set for
the minimum damper position.
OHSP
Occupied Heat Setpoint
OCSP
Occupied Cool Setpoint
UHSP
Unoccupied Heat Setpoint
V.C.ON
VAV Occupied Cool On Delta
V.C.OF
VAV Occupied Cool Off Delta
SASP
Supply Air Setpoint
SP.SP
Static Pressure Setpoint
RS.CF
EDT Reset Configuration
RTIO
Reset Ratio (if
RS.CF
= 1 or 2)
LIMT
Reset Limit (if
RS.CF
= 1 or 2)
RES.S
EDT 4-20 mA Reset Input (if
RS.CF
= 3)
SA.HI
Supply Air Set Point Hi
SA.LO
Supply Air Set Point Lo
OHSP
Occupied Heat Setpoint
OCSP
Occupied Cool Setpoint
UHSP
Unoccupied Heat Setpoint
UCSP
Unoccupied Cool Setpoint
GAP
Heat-Cool Setpoint Gap
SA.HI
Supply Air Set Point Hi
SA.LO
Supply Air Set Point Lo
L.H.ON
Demand Level Lo Heat On
H.H.ON
Demand Level Hi Heat On
L.H.OF
Demand Level Lo Heat On
L.C.ON
Demand Level Lo Cool On
H.C.ON
Demand Level Hi Cool On
L.C.OF
Demand Level Lo Cool On
EC.EN
Economizer Enabled?
EC.MN
Economizer Min.Position
EC.MX
Economizer Maximum Position
E.TRM
Economizer Trim for SumZ?
E.SEL
Econ Changeover Select
OA.E.C
OA Enthalpy Change Over Select
OA.EN
Outdoor Enthalpy Compare Value
OAT.L
High OAT Lockout Temp
O.DEW
OA Dew Point Temp Limit
ORH.S
Outside Air RH Sensor
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...