APPENDIX A — LOCAL DISPLAY TABLES
MODE — RUN STATUS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
PAGE NO.
VIEW
AUTO VIEW OF RUN STATUS
HVAC
ascii string spelling out the hvac modes
string
90,91
OCC
Occupied ?
YES/NO
OCCUPIED
forcible
90,91
MAT
Mixed Air Temperature
dF
MAT
90,91
EDT
Evaporator Discharge Tmp
dF
EDT
90,91
LAT
Leaving Air Temperature
dF
LAT
90,91
EC.C.P
Economizer Control Point
dF
ECONCPNT
50,63,70,90,91
ECN.P
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
90,91
CL.C.P
Cooling Control Point
dF
COOLCPNT
41,42,63,90,91
C.CAP
Current Running Capacity
CAPTOTAL
90,91
HT.C.P
Heating Control Point
dF
HEATCPNT
53,90,91
HT.ST
Requested Heat Stage
HT_STAGE
54-56,90,91
H.MAX
Maximum Heat Stages
HTMAXSTG
54,90,91
ECON
ECONOMIZER RUN STATUS
ECN.P
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
50,64,91
ECN.C
Economizer Act.Cmd.Pos.
0-100
%
ECONOCMD
forcible
64,91
ACTV
Economizer Active ?
YES/NO
ECACTIVE
42,50,64,91
DISA
ECON DISABLING CONDITIONS
64,91
DISA
UNAV
Econ Act. Unavailable?
YES/NO
ECONUNAV
64,91
DISA
R.EC.D
Remote Econ. Disabled ?
YES/NO
ECONDISA
64,91
DISA
DBC
DBC - OAT Lockout?
YES/NO
DBC_STAT
64,91
DISA
DEW
DEW - OA Dewpt.Lockout?
YES/NO
DEW_STAT
64,91
DISA
DDBC
DDBD- OAT > RAT Lockout?
YES/NO
DDBCSTAT
64,91
DISA
OAEC
OAEC- OA Enth Lockout?
YES/NO
OAECSTAT
64,91
DISA
DEC
DEC - Diff.Enth.Lockout?
YES/NO
DEC_STAT
64,91
DISA
EDT
EDT Sensor Bad?
YES/NO
EDT_STAT
64,91
DISA
OAT
OAT Sensor Bad ?
YES/NO
OAT_STAT
64,91
DISA
FORC
Economizer Forced ?
YES/NO
ECONFORC
64,91
DISA
SFON
Supply Fan Not On 30s ?
YES/NO
SFONSTAT
64,91
DISA
CLOF
Cool Mode Not In Effect?
YES/NO
COOL_OFF
64,91
DISA
OAQL
OAQ Lockout in Effect ?
YES/NO
OAQLOCKD
64,91
DISA
HELD
Econ Recovery Hold Off?
YES/NO
ECONHELD
64,91
DISA
DH.DS
Dehumid. Disabled Econ?
YES/NO
DHDISABL
64,91
O.AIR
OUTSIDE AIR INFORMATION
64,91
O.AIR
OAT
Outside Air Temperature
dF
OAT
forcible
64,91
O.AIR
OA.RH
Outside Air Rel. Humidity
%
OARH
forcible
64,91
O.AIR
OA.E
Outside Air Enthalpy
OAE
64,91
O.AIR
OA.D.T
OutsideAir Dewpoint Temp
dF
OADEWTMP
64,91
COOL
COOLING INFORMATION
C.CAP
Current Running Capacity
%
CAPTOTAL
46,47,49,90,92
CUR.S
Current Cool Stage
COOL_STG
46,47,63,90,92
REQ.S
Requested Cool Stage
CL_STAGE
46,47,90,92
MAX.S
Maximum Cool Stages
CLMAXSTG
46,47,90,92
DEM.L
Active Demand Limit
DEM_LIM
forcible
46-48,90,92
SUMZ
COOL CAP. STAGE CONTROL
46,47,90,92
SUMZ
SMZ
Capacity Load Factor
%
SMZ
46,47,90,92
SUMZ
ADD.R
Next Stage EDT Decrease
^F
ADDRISE
43,46,47,90,92
SUMZ
SUB.R
Next Stage EDT Increase
^F
SUBRISE
46,47,90,92
SUMZ
R.PCT
Rise Per Percent Capacity
RISE_PCT
46,47,90,92
SUMZ
Y.MIN
Cap Deadband Subtracting
Y_MINUS
46,47,90,92
SUMZ
Y.PLU
Cap Deadband Adding
Y_PLUS
46,47,90,92
SUMZ
Z.MIN
Cap Threshold Subtracting
Z_MINUS
46,47,91,92
SUMZ
Z.PLU
Cap Threshold Adding
Z_PLUS
46,47,91,92
SUMZ
H.TMP
High Temp Cap Override
HI_TEMP
46,47,91,92
SUMZ
L.TMP
Low Temp Cap Override
LOW_TEMP
46,47,91,92
SUMZ
PULL
Pull Down Cap Override
PULLDOWN
46,47,91,92
SUMZ
SLOW
Slow Change Cap Override
SLO_CHNG
47,91,92
TRIP
MODE TRIP HELPER
UN.C.S
Unoccup. Cool Mode Start
UCCLSTRT
46,53,92
UN.C.E
Unoccup. Cool Mode End
UCCL_END
46,53,92
OC.C.S
Occupied Cool Mode Start
OCCLSTRT
46,53,92
OC.C.E
Occupied Cool Mode End
OCCL_END
46,53,92
TEMP
Ctl.Temp RAT,SPT or Zone
CTRLTEMP
46,53,92
OC.H.E
Occupied Heat Mode End
OCHT_END
46,53,92
OC.H.S
Occupied Heat Mode Start
OCHTSTRT
46,53,92
UN.H.E
Unoccup. Heat Mode End
UCHT_END
46,53,92
UN.H.S
Unoccup. Heat Mode Start
UCHTSTRT
46,53,92
HVAC
ascii string spelling out the hvac modes
string
46,53,92
LINK
CCN - LINKAGE
MODE
Linkage Active - CCN
ON/OFF
MODELINK
92
L.Z.T
Linkage Zone Control Tmp
dF
LZT
92
L.C.SP
Linkage Curr. Cool Setpt
dF
LCSP
92
L.H.SP
Linkage Curr. Heat Setpt
dF
LHSP
92
HRS
COMPRESSOR RUN HOURS
HR.A1
Compressor A1 Run Hours
0-999999
HRS
HR_A1
config
92
HR.A2
Compressor A2 Run Hours
0-999999
HRS
HR_A2
config
92
HR.B1
Compressor B1 Run Hours
0-999999
HRS
HR_B1
config
92
HR.B2
Compressor B2 Run Hours
0-999999
HRS
HR_B2
config
92
STRT
COMPRESSOR STARTS
ST.A1
Compressor A1 Starts
0-999999
CY_A1
config
92
ST.A2
Compressor A2 Starts
0-999999
CY_A2
config
92
ST.B1
Compressor B1 Starts
0-999999
CY_B1
config
92
ST.B2
Compressor B2 Starts
0-999999
CY_B2
config
92
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...